Troubleshooting: Hydro Flame Thermostat
Troubleshooting: Hydro Flame Thermostat
Blower Does Not Run |
Condition | Solution |
- Temperature selector out of place
| - Re-set to desired position
|
- Thermostat wires broken or disconnected
| |
- Heat anticipator burned out
| - Dead short
- Repair short then replace thermostat
- Faulty relay drawing more than 1 amp
- Replace relay and thermostat
|
- No continuity through thermostat with contacts closed and switched on
| |
- Continuity through thermostat with contacts closed and switched on
| - Check and re-establish power to
- Reset tripped circuit breaker
- Correct poor ground
- Correct any loose wires
- Replace defective relay
- Replace defective motor
|
- Furnace cycles too quickly
| - Move anticipator to a higher amp
setting to lengthen cycle |
- High temperature variance
| - Move anticipator to a lower amp
setting to shorten cycle |